Process and comfort chillers · Adiabatic pre-cooling · Fes Chill

Industrial Chiller Systems for Process and Comfort Cooling

A chiller produces chilled water or glycol for process equipment and building air conditioning. Erdinç Klima calculates the load, selects air-cooled or water-cooled machines, designs the hydraulic circuit, installs and commissions the plant and services it; on chillers that lose capacity in summer we fit FORM Fes Chill adiabatic pre-cooling.

NAMEPLATETYPEPROCESS · COMFORT CHILLERCAPACITY20 – 5,000 kWCHILLED WATER7 / 12 °C TYPICALPRE-COOLINGFORM FES CHILL
QUICK ANSWER

An industrial chiller removes heat from water or a water-glycol mixture and rejects it outside, through an air-cooled condenser or a cooling tower. Capacities typically run from 20 kW to 5,000 kW with coefficients of performance between about 3.5 and 6.5 depending on machine type, condensing method and operating conditions. It is the standard answer wherever cooling must be delivered to several points at a controlled temperature. The two decisions that determine capital and running cost are air-cooled versus water-cooled condensing, and whether hot, dry ambient conditions justify adiabatic pre-cooling. Erdinç Klima sizes the system from the process load, supplies and commissions the plant from Istanbul and services it, in Türkiye and for export projects.

02SYSTEM DESCRIPTION

What an industrial chiller actually does

A chiller removes heat from water or a water-glycol mixture and rejects it to the outside, through an air-cooled condenser or through a cooling tower in a water-cooled system. The chilled fluid is pumped to whatever needs cooling: injection moulding tools, extruders, laser cutters, reactors, or air handling units serving the building.

FIG. 01 · CHILLER · REFRIGERATION CYCLEANIMATED DIAGRAM

SCROLL THE DRAWING →

COMPRESSOR CONDENSERHEAT → AIR / TOWER EXPANSION VALVE EVAPORATOR PROCESSmachine · mould · AHU 12 °C return7 °C supply hot gashigh pressure liquid cold mixturelow pressure 1 2 3 4
  1. 1Compressor — compresses low-pressure vapour; the component that decides efficiency and failure risk
  2. 2Condenser — rejects heat to outside air by fan (air-cooled) or to tower water (water-cooled); a fouled coil trips the high-pressure alarm
  3. 3Expansion valve — drops the pressure; the refrigerant enters the evaporator as a cold, low-pressure mixture
  4. 4Evaporator — removes heat from the process water; water returns at 12 °C and leaves at 7 °C (typical)
FIG. 01 — The four components are the same in every brand; the difference is in the controller and its parameters. Moving lines show flow direction; speed is illustrative.

The reason process plants use chilled water rather than direct expansion cooling is distribution. Water carries far more heat per unit volume than air and can be piped hundreds of metres with modest losses. One machine in the plant room can serve twenty consumers at different points, each with its own control valve.

The performance figure that matters is COP, cooling output divided by electrical input. A COP of 4.0 means 4 kW of cooling per 1 kW of electricity. COP is not a fixed property of the machine; it falls as condensing temperature rises, which is exactly what happens on a 48 °C afternoon. This is why a chiller specified on catalogue figures at 35 °C ambient can disappoint badly in the Middle East.

20 – 5,000 kW
Typical capacity range
3.5 – 6.5
COP range by type and conditions
7 / 12 °C
Typical chilled water supply / return
70 – 95 %
Adiabatic pad saturation efficiency
03SELECTION

Air-cooled or water-cooled?

Air-cooled chillers reject heat directly to ambient air and need no cooling tower, water treatment or tower maintenance. Water-cooled chillers reject heat through a cooling tower and achieve a higher COP, which makes them the usual choice above roughly 500 kW where running hours are long.

Water availability often settles the question before efficiency does. In arid inland locations the water a tower consumes may be more expensive or more restricted than the electricity an air-cooled machine uses.

TABLE 01 — Air-cooled vs water-cooled
CriterionAir-cooledWater-cooled
COPLowerHigher
Cooling tower requiredNoYes
Water consumptionNoneSignificant — evaporation and blowdown
Water treatmentNot applicableRequired — scale, corrosion, biological control
Capital costLowerHigher — tower, pumps, pipework
Typical scaleUp to ~500 kW500 kW and above
Hot dry climatesCapacity falls with ambientLess sensitive to dry-bulb
04ADIABATIC PRE-COOLING

Adiabatic pre-cooling in hot climates

Adiabatic pre-cooling wets the air entering an air-cooled condenser, lowering its temperature before it reaches the coil. Because chiller capacity and COP both fall as condensing temperature rises, reducing condenser inlet air temperature recovers capacity exactly when it is most needed: on the hottest afternoons.

The equipment is simple: a FORM Fes Chill pad module with cellulose media, typically 70 – 95 % saturation efficiency, mounted in front of the condenser with a water feed and drain. It runs only when ambient exceeds a set threshold, so water consumption is limited to peak hours rather than the whole season.

This matters most in exactly the markets we supply. In Baghdad, Riyadh or inland Anatolia the summer air is hot but dry, which is the ideal condition for adiabatic pre-cooling. It is often the difference between an existing chiller that trips on high pressure every August and one that holds its set point.

NOTE

Water quality decides whether this works long term. Adiabatic modules concentrate minerals as water evaporates, so hard feed water scales the pads and the condenser fins. In hard-water regions plan feed-water conditioning or a scale-control programme from the start. A retrofitted module that blocks a condenser with limescale makes the original problem worse, not better.

05SIZING INPUTS

What we need to size a system

Chiller selection starts from the process load, not the building area. We need the heat to be removed in kW, the required chilled-water flow and supply temperature, whether glycol is needed for low temperatures or frost protection, and the site design ambient temperature.

  • Cooling load — in kW, or the process data from which it can be calculated
  • Chilled water temperature — supply and return; this sets evaporating temperature and therefore COP
  • Glycol requirement — concentration affects capacity and pump sizing
  • Design ambient — the nearest city is enough; we use recognised design weather data
  • Load profile — constant or variable; variable loads usually justify inverter-driven compressors
  • Redundancy — whether production can tolerate a stopped chiller, which decides N+1 arrangements
06SERVICE

Commissioning, service and refrigerant compliance

The team that sizes the plant installs and commissions it, and stays responsible for maintenance: condenser cleaning, refrigerant circuit checks, water quality and control verification, typically twice a year on continuous duty. Chillers usually hold the largest refrigerant charges on a site, so periodic F-Gas leak checks and records are part of the same service.

For export projects we attend site for commissioning on larger installations; for smaller ones we provide selection, layout and commissioning guidance remotely, with spare parts shipped from stock in Istanbul. In Türkiye the technical team reaches Istanbul's Anatolian side within 30 minutes and works nationwide on a project basis.

07RELATED PAGES

Related pages

The other systems on this site, and the Turkish version of this page.

  • 07-A

    All industrial cooling systems

    Evaporative cooling, panel air conditioners, chillers, smoke ventilation and F-Gas compliance from one supplier.

    Go to the overview →
  • 07-B

    F-Gas leak detection and compliance

    Where most large refrigerant charges sit: CO₂-equivalent bands, leak-check intervals and fixed detection.

    F-Gas compliance →
  • 07-C

    Evaporative cooling

    For halls where chilled water is not justified: fresh-air cooling with no compressor.

    Evaporative cooling →
  • 07-D

    Turkish version of this page

    Chiller cooling page in Turkish, with pre-cooling module selection and service details.

    Turkish version →
08FREQUENTLY ASKED QUESTIONS

Frequently asked questions

COP, condensing method, adiabatic pre-cooling, glycol and service questions from plant and maintenance managers.

09LEAVE THE INSTALLATION TO US

Send us the process load, not the room size

Cooling duty, water temperatures and your design ambient are enough for a first-pass machine selection with realistic derated capacity. Technical consultation by phone or WhatsApp is free; site visits are quoted.

20+ years · authorised Rittal service partner · Istanbul, Türkiye

Address
Esatpaşa Mah., Binikli Sk., Alibey Apt. No: 2/A-B-C, 34704 Ataşehir / İstanbul
Hours
Mon–Fri 09:00–18:00 · Sat by appointment

SON GÜNCELLEME: · İçerik Erdinç Klima teknik ekibince hazırlanır ve üretici dokümanlarıyla doğrulanır.

YARDIMCI ZEKÂ

Bu sitedeki yardımcı zekâ, MIOE Elektronik ve Yazılım'ın işidir.

"Bilgi sor" kutusu sorulara sitedeki sayfalardan, kataloglardan ve föylerden kaynak göstererek cevap verir. Aynı yapıyı kendi sitenize kurdurmak için MIOE'yi arayın.